Technical data | IE2808 | IE2808-0001 |
---|
Number of outputs | 16 |
Output connections | D-sub socket, 25-pin |
Load type | ohmic, inductive, lamp load |
Nominal output voltage | 24 V DC (-15 %/+20 %) |
Max. output current | 0.5 A per channel, individually short-circuit-proof, total current max. 4 A |
Short circuit current | max. 1.5 A |
Auxiliary power current | typ. 30 mA |
Current consumption from US (without sensor current) | 25 mA |
Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Error handling | fault acknowledgement by master required | automatically |
Bit width in the process image | 16 outputs, 16 inputs (diagnostics) optional: control/status |
Electrical isolation | channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals | CE, UL |